Power Generation

Power Generation Product Finder

Application Group Types

The followings are an explanation of the various application group types.
Standby power

Standby power (3D)  

Load

Load factor

10% overload (ICXN)

Max. operating hours (per year)

Uptime compliant

mtu  Power Generation

variable

≤ 85%

no

500 h  

Tier I & Tier II

ISO 8528-1 (ESP)

variable

≤ 70%

not specified

200 h

not specified

Prime power for stationary emergency (3E)

Load

Load factor

10% overload (ICXN)

Max. operating hours (per year)

Uptime compliant

mtu  Power Generation

variable

≤ 85%

yes

500 h  

Tier I & Tier II

ISO 8528-1 (ESP)

variable

≤ 70%

not specified

200 h

not specified

Data center continuous power (3F)

Load

Load factor

10% overload (ICXN)

Max. operating hours (per year)

Uptime compliant

mtu  Power Generation

continuous  

≤ 100%

yes

unlimited

Tier I - Tier IV

ISO 8528-1 (DCP)

continuous or variable

≤ 100%

not specified

unlimited

not specified

Continuous/Prime/Grid stability power

Continuous power + CHP (3A)

Load

Load factor

10% overload (ICXN)

Max. operating hours (per year)

mtu  Power Generation

constant

≤ 100%

Gas: no, Diesel: yes

unlimited

ISO 8528-1 (ESP)

constant

≤ 100%

not specified

unlimited

Prime power (3B)

Load

Load factor

10% overload (ICXN)

Max. operating hours (per year)

mtu  Power Generation

variable

≤ 75%

yes

unlimited

ISO 8528-1 (PRP)

variable

≤ 70%

yes

unlimited

Grid stability power (3G)

Load

Load factor

10% overload (ICXN)

Max. operating hours (per year)

mtu  Power Generation

continuous

≤ 100%

Gas: no, Diesel: yes

1000 h; 500 h with 100% load w/o interruption

ISO 8528-1 (LTP)

continuous

≤ 100%

not specified

500 h

Diesel Generator Sets

Product results are displayed by power range from lowest to highest. To see fewer results, select one or more filters.
Power
Range(kW)
  • Standby power
  • Prime power for stationary emergency
  • Data center continuous power
  • Prime power
  • EPA Tier 4, SCAQMD
  • EPA Tier 3
  • EPA Tier 3, SCAQMD
  • EPA Tier 2
  • EPA Tier 2, SCAQMD
  • EPA Tier 2 compliant, SCAQMD
  • Fuel consumption optimized
  • 40°C
  • 43°C
  • 45°C
  • 48°C
  • 50°C
  • Series 0096
  • Series 0113
  • Series 0120
  • Series 0150
  • Series 0225
  • Series 1600
  • Series 2000
  • Series 4000
  • Clear filter
  • 12V1600 DS550
  • 12V1600 DS600
  • 12V1600 DS750
  • 12V1600 DS800
  • 12V1600 DS900
  • 12V4000 DS1250
  • 12V4000 DS1500
  • 12V4000 DS1750
  • 16V2000 DS1000
  • 16V2000 DS1250
  • 16V4000 DS2000
  • 16V4000 DS2250
  • 16V4000 DS2500
  • 18V2000 DS1250
  • 20V4000 DS2500
  • 20V4000 DS2800
  • 20V4000 DS3000
  • 20V4000 DS3250
  • 3R0096 DS30
  • 4R0113 DS100
  • 4R0113 DS40
  • 4R0113 DS50
  • 4R0113 DS60
  • 4R0113 DS80
  • 4R0120 DS100
  • 4R0120 DS125
  • 4R0120 DS80
  • 6R0113 DS150
  • 6R0113 DS180
  • 6R0113 DS200
  • 6R0120 DS150
  • 6R0120 DS180
  • 6R0120 DS200
  • 6R0150 DS230
  • 6R0150 DS250
  • 6R0150 DS275
  • 6R0150 DS300
  • 6R0225 DS350
  • 6R0225 DS400
  • Clear filter
  • Standby power
  • Prime power for stationary emergency
  • Data center continuous power
  • Prime power
  • Grid stability power
  • Continuous power

Info

See the explanation section at the top of the page.

27 kW Prime power for stationary emergency EPA 40CFRP60 50°C Series 0096 3R0096 DS30
30 kW Standby power EPA 40CFRP60 50°C Series 0096 3R0096 DS30
40 kW Prime power for stationary emergency EPA Tier 3, SCAQMD 50°C Series 0113 4R0113 DS40
40 kW Standby power EPA Tier 3, SCAQMD 50°C Series 0113 4R0113 DS40
40 kW Standby power EPA Tier 3 50°C Series 0113 4R0113 DS40
40 kW Prime power for stationary emergency EPA Tier 3 50°C Series 0113 4R0113 DS40
45 kW Prime power for stationary emergency EPA Tier 3, SCAQMD 50°C Series 0113 4R0113 DS50
45 kW Prime power for stationary emergency EPA Tier 3 50°C Series 0113 4R0113 DS50
50 kW Standby power EPA Tier 3, SCAQMD 50°C Series 0113 4R0113 DS50
50 kW Standby power EPA Tier 3 50°C Series 0113 4R0113 DS50
55 kW Prime power for stationary emergency EPA Tier 3 50°C Series 0113 4R0113 DS60
60 kW Standby power EPA Tier 3 50°C Series 0113 4R0113 DS60
72 kW Prime power EPA Tier 3, SCAQMD 50°C Series 0120 4R0120 DS80
80 kW Standby power EPA Tier 3, SCAQMD 50°C Series 0113 4R0113 DS80
80 kW Prime power for stationary emergency EPA Tier 3, SCAQMD 50°C Series 0113 4R0113 DS80
80 kW Standby power EPA Tier 3, SCAQMD 50°C Series 0120 4R0120 DS80
90 kW Prime power for stationary emergency EPA Tier 3, SCAQMD 50°C Series 0113 4R0113 DS100
90 kW Prime power EPA Tier 3, SCAQMD 50°C Series 0120 4R0120 DS100
100 kW Standby power EPA Tier 3, SCAQMD 50°C Series 0113 4R0113 DS100
100 kW Standby power EPA Tier 3, SCAQMD 50°C Series 0120 4R0120 DS100
111 kW Prime power EPA Tier 3, SCAQMD 50°C Series 0120 4R0120 DS125
125 kW Standby power EPA Tier 3, SCAQMD 50°C Series 0120 4R0120 DS125
135 kW Prime power for stationary emergency EPA Tier 3, SCAQMD 50°C Series 0113 6R0113 DS150
135 kW Prime power EPA Tier 3, SCAQMD 50°C Series 0120 6R0120 DS150
150 kW Standby power EPA Tier 3, SCAQMD 50°C Series 0113 6R0113 DS150
150 kW Standby power EPA Tier 3, SCAQMD 50°C Series 0120 6R0120 DS150
163 kW Prime power EPA Tier 3, SCAQMD 50°C Series 0120 6R0120 DS180
180 kW Standby power EPA Tier 3, SCAQMD 50°C Series 0113 6R0113 DS180
180 kW Prime power for stationary emergency EPA Tier 3, SCAQMD 50°C Series 0113 6R0113 DS180
180 kW Standby power EPA Tier 3, SCAQMD 50°C Series 0120 6R0120 DS180
180 kW Prime power EPA Tier 3, SCAQMD 50°C Series 0120 6R0120 DS200
200 kW Standby power EPA Tier 3, SCAQMD 50°C Series 0113 6R0113 DS200
200 kW Standby power EPA Tier 3, SCAQMD 50°C Series 0120 6R0120 DS200
210 kW Prime power for stationary emergency EPA Tier 3, SCAQMD 50°C Series 0150 6R0150 DS230
210 kW Prime power EPA Tier 4, SCAQMD 50°C Series 0150 6R0150 DS230 With aftertreatment
230 kW Standby power EPA Tier 3, SCAQMD 50°C Series 0150 6R0150 DS230
230 kW Prime power for stationary emergency EPA Tier 3, SCAQMD 50°C Series 0150 6R0150 DS250
230 kW Standby power EPA Tier 4, SCAQMD 50°C Series 0150 6R0150 DS230 With aftertreatment
230 kW Prime power EPA Tier 4, SCAQMD 50°C Series 0150 6R0150 DS250 With aftertreatment
250 kW Standby power EPA Tier 3, SCAQMD 50°C Series 0150 6R0150 DS250
250 kW Prime power for stationary emergency EPA Tier 3, SCAQMD 50°C Series 0150 6R0150 DS275
250 kW Standby power EPA Tier 4, SCAQMD 50°C Series 0150 6R0150 DS250 With aftertreatment
250 kW Prime power EPA Tier 4, SCAQMD 50°C Series 0150 6R0150 DS275 With aftertreatment
265 kW Prime power EPA Tier 4, SCAQMD 50°C Series 0150 6R0150 DS300 With aftertreatment
275 kW Standby power EPA Tier 3, SCAQMD 50°C Series 0150 6R0150 DS275
275 kW Standby power EPA Tier 4, SCAQMD 50°C Series 0150 6R0150 DS275 With aftertreatment
300 kW Standby power EPA Tier 3, SCAQMD 50°C Series 0150 6R0150 DS300
300 kW Standby power EPA Tier 4, SCAQMD 50°C Series 0150 6R0150 DS300 With aftertreatment
325 kW Prime power EPA Tier 4, SCAQMD 50°C Series 0225 6R0225 DS350 With aftertreatment
350 kW Standby power EPA Tier 3, SCAQMD 50°C Series 0225 6R0225 DS350
350 kW Standby power EPA Tier 4, SCAQMD 50°C Series 0225 6R0225 DS350 With aftertreatment
365 kW Prime power EPA Tier 4, SCAQMD 50°C Series 0225 6R0225 DS400 With aftertreatment
400 kW Standby power EPA Tier 3, SCAQMD 50°C Series 0225 6R0225 DS400
400 kW Standby power EPA Tier 4, SCAQMD 50°C Series 0225 6R0225 DS400 With aftertreatment
500 kW Prime power EPA Tier 2 50°C Series 1600 12V1600 DS550
550 kW Standby power EPA Tier 2, SCAQMD 50°C Series 1600 12V1600 DS550
550 kW Prime power EPA Tier 2 50°C Series 1600 12V1600 DS600
600 kW Standby power EPA Tier 2, SCAQMD 50°C Series 1600 12V1600 DS600
690 kW Prime power for stationary emergency EPA Tier 2 50°C Series 1600 12V1600 DS750
690 kW Data center continuous power EPA Tier 2 50°C Series 1600 12V1600 DS750
730 kW Prime power for stationary emergency EPA Tier 2 50°C Series 1600 12V1600 DS800
730 kW Data center continuous power EPA Tier 2 50°C Series 1600 12V1600 DS800
750 kW Standby power EPA Tier 2 50°C Series 1600 12V1600 DS750
800 kW Standby power EPA Tier 2 50°C Series 1600 12V1600 DS800
820 kW Prime power for stationary emergency EPA Tier 2 50°C Series 1600 12V1600 DS900
820 kW Data center continuous power EPA Tier 2 50°C Series 1600 12V1600 DS900
900 kW Prime power EPA Tier 2 50°C Series 2000 16V2000 DS1000
900 kW Data center continuous power EPA Tier 2 50°C Series 2000 16V2000 DS1000
900 kW Standby power EPA Tier 2 50°C Series 1600 12V1600 DS900
1000 kW Standby power EPA Tier 2, SCAQMD 50°C Series 2000 16V2000 DS1000
1000 kW Prime power Fuel consumption optimized 50°C Series 2000 18V2000 DS1250
1135 kW Data center continuous power EPA Tier 2, SCAQMD 50°C Series 4000 12V4000 DS1250
1135 kW Data center continuous power Fuel consumption optimized 50°C Series 4000 12V4000 DS1250
1250 kW Standby power EPA Tier 2, SCAQMD 40°C Series 2000 16V2000 DS1250
1250 kW Standby power EPA Tier 2, SCAQMD 50°C Series 4000 12V4000 DS1250
1250 kW Standby power Fuel consumption optimized 50°C Series 4000 12V4000 DS1250
1250 kW Standby power EPA Tier 2, SCAQMD 50°C Series 2000 18V2000 DS1250
1400 kW Data center continuous power EPA Tier 2, SCAQMD 50°C Series 4000 12V4000 DS1500
1400 kW Data center continuous power EPA Tier 2, SCAQMD 40°C Series 4000 12V4000 DS1500
1400 kW Data center continuous power Fuel consumption optimized 40°C Series 4000 12V4000 DS1500
1400 kW Data center continuous power Fuel consumption optimized 50°C Series 4000 12V4000 DS1500
1500 kW Standby power EPA Tier 2, SCAQMD 50°C Series 4000 12V4000 DS1500
1500 kW Standby power EPA Tier 2, SCAQMD 40°C Series 4000 12V4000 DS1500
1500 kW Standby power Fuel consumption optimized 40°C Series 4000 12V4000 DS1500
1500 kW Standby power Fuel consumption optimized 50°C Series 4000 12V4000 DS1500
1600 kW Data center continuous power EPA Tier 2, SCAQMD 50°C Series 4000 12V4000 DS1750
1600 kW Data center continuous power EPA Tier 2, SCAQMD 40°C Series 4000 12V4000 DS1750
1600 kW Data center continuous power Fuel consumption optimized 40°C Series 4000 12V4000 DS1750
1600 kW Data center continuous power Fuel consumption optimized 50°C Series 4000 12V4000 DS1750
1750 kW Standby power EPA Tier 2, SCAQMD 50°C Series 4000 12V4000 DS1750
1750 kW Standby power EPA Tier 2, SCAQMD 40°C Series 4000 12V4000 DS1750
1750 kW Standby power Fuel consumption optimized 40°C Series 4000 12V4000 DS1750
1750 kW Standby power Fuel consumption optimized 50°C Series 4000 12V4000 DS1750
1825 kW Data center continuous power EPA Tier 2, SCAQMD 50°C Series 4000 16V4000 DS2000
1825 kW Data center continuous power EPA Tier 2, SCAQMD 45°C Series 4000 16V4000 DS2000
1825 kW Data center continuous power Fuel consumption optimized 45°C Series 4000 16V4000 DS2000
1825 kW Data center continuous power Fuel consumption optimized 50°C Series 4000 16V4000 DS2000
2000 kW Standby power EPA Tier 2, SCAQMD 50°C Series 4000 16V4000 DS2000
2000 kW Standby power EPA Tier 2, SCAQMD 45°C Series 4000 16V4000 DS2000
2000 kW Standby power Fuel consumption optimized 45°C Series 4000 16V4000 DS2000
2000 kW Standby power Fuel consumption optimized 50°C Series 4000 16V4000 DS2000
2045 kW Data center continuous power EPA Tier 2, SCAQMD 50°C Series 4000 16V4000 DS2250
2045 kW Data center continuous power EPA Tier 2, SCAQMD 40°C Series 4000 16V4000 DS2250
2045 kW Data center continuous power Fuel consumption optimized 40°C Series 4000 16V4000 DS2250
2045 kW Data center continuous power Fuel consumption optimized 50°C Series 4000 16V4000 DS2250
2250 kW Standby power EPA Tier 2, SCAQMD 50°C Series 4000 16V4000 DS2250
2250 kW Standby power EPA Tier 2, SCAQMD 40°C Series 4000 16V4000 DS2250
2250 kW Standby power Fuel consumption optimized 40°C Series 4000 16V4000 DS2250
2250 kW Standby power Fuel consumption optimized 50°C Series 4000 16V4000 DS2250
2275 kW Data center continuous power EPA Tier 2, SCAQMD 50°C Series 4000 20V4000 DS2500
2275 kW Data center continuous power Fuel consumption optimized 50°C Series 4000 20V4000 DS2500
2500 kW Data center continuous power EPA Tier 2, SCAQMD 50°C Series 4000 20V4000 DS2800
2500 kW Standby power EPA Tier 2, SCAQMD 45°C Series 4000 16V4000 DS2500
2500 kW Standby power Fuel consumption optimized 45°C Series 4000 16V4000 DS2500
2500 kW Standby power EPA Tier 2, SCAQMD 50°C Series 4000 20V4000 DS2500
2500 kW Standby power Fuel consumption optimized 50°C Series 4000 20V4000 DS2500
2500 kW Data center continuous power EPA Tier 2, SCAQMD 48°C Series 4000 20V4000 DS2800
2500 kW Data center continuous power Fuel consumption optimized 48°C Series 4000 20V4000 DS2800
2500 kW Data center continuous power Fuel consumption optimized 50°C Series 4000 20V4000 DS2800
2790 kW Standby power EPA Tier 2, SCAQMD 50°C Series 4000 20V4000 DS2800
2790 kW Data center continuous power EPA Tier 2, SCAQMD 50°C Series 4000 20V4000 DS3000
2790 kW Standby power Fuel consumption optimized 50°C Series 4000 20V4000 DS2800
2790 kW Data center continuous power Fuel consumption optimized 50°C Series 4000 20V4000 DS3000
2800 kW Standby power EPA Tier 2, SCAQMD 48°C Series 4000 20V4000 DS2800
2800 kW Standby power Fuel consumption optimized 48°C Series 4000 20V4000 DS2800
2800 kW Data center continuous power EPA Tier 2, SCAQMD 45°C Series 4000 20V4000 DS3000
2800 kW Data center continuous power Fuel consumption optimized 45°C Series 4000 20V4000 DS3000
3000 kW Standby power EPA Tier 2, SCAQMD 50°C Series 4000 20V4000 DS3000
3000 kW Standby power EPA Tier 2, SCAQMD 45°C Series 4000 20V4000 DS3000
3000 kW Standby power Fuel consumption optimized 45°C Series 4000 20V4000 DS3000
3000 kW Standby power Fuel consumption optimized 50°C Series 4000 20V4000 DS3000
3250 kW Standby power EPA Tier 2, SCAQMD 43°C Series 4000 20V4000 DS3250
3250 kW Standby power Fuel consumption optimized 43°C Series 4000 20V4000 DS3250
No results found Try adjusting the filters to find what you’re looking for.
Power
Range(kVA)
  • Standby power
  • Prime power for stationary emergency
  • Data center continuous power
  • Prime power
  • Grid stability power
  • Continuous power
  • Fuel consumption optimized
  • NEA (ORDE) optimized
  • NOx emission optimized
  • Exhaust-optimized
  • Exhaust emission EU 97/68 EC Stage II compliant
  • EPA Tier 2 optimized
  • Tier 2 compliant
  • 40CFRP60
  • Series 1600
  • Series 2000
  • Series 4000
  • Clear filter
  • 12V1600 DS1000
  • 12V1600 DS650
  • 12V1600 DS715
  • 12V1600 DS825
  • 12V1600 DS880
  • 12V2000 DS1000
  • 12V2000 DS825
  • 12V4000 DS1650
  • 12V4000 DS1750
  • 12V4000 DS2000
  • 12V4000 DS2250
  • 16V2000 DS1000
  • 16V2000 DS1100
  • 16V2000 DS1250
  • 16V4000 DS2250
  • 16V4000 DS2500
  • 16V4000 DS2750
  • 16V4000DS2750
  • 18V2000 DS1400
  • 20V4000 DS3600
  • 20V4000 DS4000
  • 20V4000 DS2750
  • 20V4000 DS3100
  • 20V4000 DS3300
  • 20V4000 DS3600
  • 20V4000 DS4000
  • Clear filter
  • Air charge-air cooling
  • Water charge-air cooling
  • Water-to-Air charge cooling

Info

See the explanation section at the top of the page.

Europe, Africa, Asia and Australia
590 kVA Prime Power NOx emission optimized Series 1600 12V1600 DS650 Air charge-air cooling
590 kVA Prime Power Fuel consumption optimized Series 1600 12V1600 DS650 Air charge-air cooling
590 kVA Prime Power NEA (ORDE) optimized Series 1600 12V1600 DS650 Air charge-air cooling
590 kVA Prime power for stationary emergency NOx emission optimized Series 1600 12V1600 DS650 Air charge-air cooling
590 kVA Prime power for stationary emergency Fuel consumption optimized Series 1600 12V1600 DS650 Air charge-air cooling
590 kVA Prime power for stationary emergency NEA (ORDE) optimized Series 1600 12V1600 DS650 Air charge-air cooling
590 kVA Data center continuous power NOx emission optimized Series 1600 12V1600 DS650 Air charge-air cooling
590 kVA Data center continuous power Fuel consumption optimized Series 1600 12V1600 DS650 Air charge-air cooling
590 kVA Data center continuous power NEA (ORDE) optimized Series 1600 12V1600 DS650 Air charge-air cooling
650 kVA Standby power Fuel consumption optimized Series 1600 12V1600 DS650 Air charge-air cooling
650 kVA Standby power NEA (ORDE) optimized Series 1600 12V1600 DS650 Air charge-air cooling
650 kVA Prime Power NOx emission optimized Series 1600 12V1600 DS715 Air charge-air cooling
650 kVA Prime Power Fuel consumption optimized Series 1600 12V1600 DS715 Air charge-air cooling
650 kVA Prime Power NEA (ORDE) optimized Series 1600 12V1600 DS715 Air charge-air cooling
650 kVA Prime power for stationary emergency NOx emission optimized Series 1600 12V1600 DS715 Air charge-air cooling
650 kVA Prime power for stationary emergency Fuel consumption optimized Series 1600 12V1600 DS715 Air charge-air cooling
650 kVA Prime power for stationary emergency NEA (ORDE) optimized Series 1600 12V1600 DS715 Air charge-air cooling
650 kVA Data center continuous power NOx emission optimized Series 1600 12V1600 DS715 Air charge-air cooling
650 kVA Data center continuous power Fuel consumption optimized Series 1600 12V1600 DS715 Air charge-air cooling
650 kVA Data center continuous power NEA (ORDE) optimized Series 1600 12V1600 DS715 Air charge-air cooling
715 kVA Standby power Fuel consumption optimized Series 1600 12V1600 DS715 Air charge-air cooling
715 kVA Standby power NEA (ORDE) optimized Series 1600 12V1600 DS715 Air charge-air cooling
750 kVA Continuous power Fuel consumption optimized Series 2000 12V2000 DS1000 Air charge-air cooling
750 kVA Prime Power Fuel consumption optimized Series 1600 12V1600 DS825 Air charge-air cooling
750 kVA Prime Power NEA (ORDE) optimized Series 1600 12V1600 DS825 Air charge-air cooling
750 kVA Prime Power EPA Tier 2 optimized Series 1600 12V1600 DS825 Air charge-air cooling
750 kVA Prime power for stationary emergency Fuel consumption optimized Series 1600 12V1600 DS825 Air charge-air cooling